Specifications

Vibration max g
0.5
Switching time s
1
Humidity percent
90
Overload time (min)
1
Power range max kw
3000
Power range min kw
400
Protection class
IP30
Analog input (count)
4
Input power factor
0.95
Altitude derating m
1000
Digital input (count)
16
Power off hold time s
2
Digital output (count)
8
Input line voltage kv
3.0/6.0/10.0
Input voltage u4 n max (v)
800
Input voltage u4 n min (v)
517
Input voltage u6 n max (v)
1200
Input voltage u6 n min (v)
816
Output line voltage kv
3.0/6.0/10.0
Harmonic content percent
5
Max bypass units per phase
2
Storage temperature max c
70
Storage temperature min c
-20
Overload capacity percent
200
Analog output current (count)
4
Analog output voltage (count)
4
Input voltage error percent
15
Operating temperature max c
50
Operating temperature min c
0
Acceleration time range max s
3200
Acceleration time range min s
0.1
Speed adjustment range max hz
120
Speed adjustment range min hz
0.5
Output frequency resolution hz
0.01
Max starting current times rated
2
Closed loop speed control accuracy
0.001
Input side high harmonics6k v percent
4
Input side high harmonics10k v percent
3

Overview

The ME800 series high voltage inverter is designed and manufactured by Shanghai Singlina Xinshida Motor Co., Ltd. It integrates power electronics and vector control technology. It suppresses input harmonic current via a phase-shifting rectifier transformer and achieves voltage superposition through cascaded H-bridge power units. It provides high-voltage sine wave output to directly drive high-voltage motors without filters, meeting IEC 519-1992 and GB/T 12668.4-2006 harmonic standards.

Key features

  • Flexible terminal expansion without PLC
  • Vector control with encoder feedback
  • High-quality motor drive with sinusoidal current output
  • Low harmonic content (<5%) without output filter
  • Speed tracking for direct start on running motor
  • Mechanical unit bypass (max 2 per phase) for continuous operation
  • Undisturbed switching between inverter and mains power
  • Curve display on touchscreen (current, speed, power)
  • Bus voltage self-balancing reduces deceleration time to ~66%
  • Power-off hold for 2 seconds with auto-recovery