Other

AS510 AFE Rectifier Feedback Unit

by Step Ia

AS510 AFE Rectifier Feedback Unit

Specifications

Mounting
Cabinet mount
Altitude max m
1000
Max altitude m
3000
Cooling method
Forced air cooling
Harmonic percent
Less than 5%
Max temperature c
50
Power range max kw
450
Power range min kw
30
Adapter power30 kw
30
Adapter power55 kw
55
Input power factor
0.95
Overload capacity
150% 1 min
Adapter power110 kw
110
Adapter power185 kw
185
Adapter power220 kw
220
Adapter power280 kw
280
Adapter power355 kw
355
Adapter power450 kw
450
Input power voltage
380V~460V
Humidity max percent
95
Humidity min percent
5
Rated capacity30 kva
38
Rated capacity55 kva
76
Input frequency max hz
65
Input frequency min hz
45
Rated capacity110 kva
142
Rated capacity185 kva
209
Rated capacity220 kva
253
Rated capacity280 kva
308
Rated capacity355 kva
358
Rated capacity450 kva
487
Vibration low freq ms2
3.5
Protection class4 t055
IP20
Rated input current30 (a)
65
Rated input current55 (a)
128
Vibration high freq ms2
10
Carrier frequency max hz
8000
Carrier frequency min hz
6000
Rated input current110 (a)
240
Rated input current185 (a)
352
Rated input current220 (a)
426
Rated input current280 (a)
520
Rated input current355 (a)
650
Rated input current450 (a)
820
Rated output current30 (a)
58
Rated output current55 (a)
115
Vibration low freq hz max
9
Vibration low freq hz (min)
2
Ambient temperature max c
40
Ambient temperature min c
-10
Rated output current110 (a)
215
Rated output current185 (a)
316
Rated output current220 (a)
383
Rated output current280 (a)
467
Rated output current355 (a)
584
Rated output current450 (a)
737
Storage temperature max c
70
Storage temperature min c
-40
Vibration high freq hz max
120
Vibration high freq hz (min)
9
Altitude derating threshold m
1000
Protection class4 t110 and above
IP00
Temperature derating threshold c
40
Controllable voltage range max vdc
740
Controllable voltage range min vdc
600
Altitude derating rate percent per100m
1
Temperature derating rate percent per c
2

Overview

The AS510 AFE Rectifier Feedback Unit is a power supply and feedback unit providing constant DC voltage regardless of load. It enables four-quadrant operation and feeds energy back to the incoming side. Power range: 30kW-450kW at 400V input. Features controlled rectifier technology, THDi <5%, energy feedback, standard LCL filter, and charging resistor. Suitable for harmonic suppression and energy feedback applications like pumps, fans, compressors, hoisting, winches, conveyors, test benches, and turbines.

Key features

  • Controlled rectifier technology
  • THDi < 5%
  • Energy feedback technology
  • Standard LCL filter
  • Standard charging resistor
  • Reduces current harmonics
  • Reduces reactive power: Cos φ and λ = 1
  • Overload capacity 150% for 1 minute
Manufacturer page

More from Step Ia

Back to Step Ia