The rapid growth of artificial intelligence (AI)-driven data centers is reshaping electricity demand patterns. This is achieved by introducing fast, multi-gigawatt load ramps that challenge the stability and resilience of modern power systems. Traditional resilience frameworks focus mainly on physical outages and largely overlook these emerging digital-era disturbances. This paper proposes a unified two-stage, risk-aware distributionally robust optimization (DRO)-MILP framework that coordinates the pre-allocation and post-event dispatch of Flexible Capacity Modules (FCMs), including BESS, fast-ramping generation, demand response, and potential long-duration storage. Stage-I optimally positions FCMs using DRO with CVaR to hedge against uncertain AI load surges. Stage-II models real-time stabilization following stochastic demand-shock scenarios, minimizing imbalance, unserved energy, and restoration penalties. The framework is designed to be applied on IEEE 33-bus system or expanded for scalability to larger IEEE test feeders capable of representing AI-scale loads. This contributes a scalable planning tool for resilient, AI-integrated distribution grids.