Home /Research /Impact of Grid-Forming Inverters on Protective Relays: A Perspective for Current Limiting Control Design
OTHER

Impact of Grid-Forming Inverters on Protective Relays: A Perspective for Current Limiting Control Design

Yifei Li, Heng Wu, Xiongfei Wang

Year
2025
Access
Open access

Abstract

Grid-forming (GFM) inverters can significantly alter the fault characteristics of power systems, which challenges the proper function of protective relays. This paper gives a holistic analysis of the interaction between GFM inverter-based resources (IBRs) and the supervising elements in protective relays, including directional and phase selection elements. It is revealed that the current limiting control (CLC) that is based on the current reference saturation method, adversely affects the performance of supervising elements that rely on the negative-sequence quantities. In contrast, adopting highly inductive virtual impedance in the CLC enables a reliable operation of such elements. This finding provides insights into the design of CLC for GFM IBRs from a protection perspective. It is further found that even with a highly inductive virtual impedance, the altered virtual impedance dynamics introduced by the CLC can still lead to malfunctions of the incremental quantity-based supervising elements. These theoretical findings are corroborated by simulations and controller hardware-in-the-loop (CHIL) tests.

Keywords

eess.SY