GCS
Specifications
- Pollution degree
- 3
- Enclosure depth (mm)
- 600, 800, 1000
- Enclosure width (mm)
- 400, 600, 800, 1000
- Rated frequency hz
- 50 / 60
- Enclosure height (mm)
- 2200
- Overvoltage category
- Category III
- Rated insulation voltage ac (v)
- AC 690V, 1000V
- Enclosure protection degree ip
- IP30, IP40
- Vertical busbar rated voltage (v)
- 1000
- Horizontal busbar rated current (a)
- ≤ 4000
- Rated impulse withstand voltage kv
- 8
- Rated operating voltage main circuit ac (v)
- 380V, 200V
- Rated peak withstand current vertical ka
- 105
- Rated peak withstand current horizontal ka
- 176
- Rated operating voltage auxiliary circuit dc (v)
- 200V, 100V
- Rated short time withstand current vertical ka
- 80
- Rated short time withstand current horizontal ka
- 80
Overview
GCS Type Low-Voltage Draw-Out Switchgear is suitable for power conversion, distribution, and control in low-voltage power distribution systems of power plants, substations, petrochemical sectors, industrial plants, mines, enterprises, and high-rise buildings. It serves applications such as power distribution, motor control centers, and capacitor compensation. The GCS low-voltage withdrawable switchgear features high switching capacity, excellent dynamic and thermal stability, advanced and rational structure, flexible electrical configurations, high protection rating, enhanced safety, and convenient maintenance. It also delivers superior technical performance metrics. This product complies with standards including IEC 60439-1, GB 7251.1, GB 7251.12, and JBT 9661.
Key features
- ▸Low-voltage draw-out switchgear for power conversion, distribution, and control
- ▸High switching capacity, excellent dynamic and thermal stability
- ▸Advanced and rational structure, flexible electrical configurations
- ▸High protection rating (IP30/IP40), enhanced safety
- ▸Convenient maintenance and superior technical performance
- ▸Complies with IEC 60439-1, GB 7251.1, GB 7251.12, JBT 9661