Condition Monitoring of Cap and Pin Insulator String by Electric Field Mapping Using Electro-Optical Probes With FEA Model Validation
Fang Liu, Erwin Lopez, Ramy S. A. Afia, Andrew West, Harry McDonald, Vidyadhar Peesapati, Siniša Djurović, Ian Cotton, Khristopher Kabbabe, Stephen Mbisike, D. D. Stewart, Lionel Duvillaret
- 发表年份
- 2025
- 引用次数
- 2
摘要
Cap and pin insulators are widely used in electricity transmission towers in power systems and are one of their key functional elements. This paper reports on a successful application of using electric field as an index to detect and locate shorted insulator units in a cap and pin string. Electro-optical (EO) probes were used to measure the electrical field, and a six axis robotic arm, holding the probes, enabled electrical field mapping at different spatial locations. The electric field distribution was first plotted according to the measurements performed by EO probes travelling along straight lines parallel to the string, and then a closer examination between insulator sheds was conducted to evaluate the possibility of higher accuracy locating of shorted insulator units. The measured changes in electric field distribution were compared with predictions from corresponding electrostatic finite element analysis (FEA) models, confirming the ability of locating shorted units in the string based on observation of the field spatial distribution change. The electric field monitoring system was also further developed to achieve operator-free and automated data acquisition and recording. The reported methodology exhibits promising potential in live condition monitoring of insulator strings in high voltage (HV) towers.
关键词
相关论文
Statistical Learning Theory
Yuhai Wu, Vladimir Vapnik
1999
Fractional Differential Equations
Igor Podlubný
2025
Applied Nonlinear Control
Jean-Jacques Slotine, Weiping Li
1991
Genetic Programming: On the Programming of Computers by Means of Natural Selection
John R. Koza
1992