首页 /研究 /Experimental Characterisation of Distributed Reactive Power Sharing under Communication-Induced Stress in Parallel Grid-Forming Inverters
OTHER

Experimental Characterisation of Distributed Reactive Power Sharing under Communication-Induced Stress in Parallel Grid-Forming Inverters

E. D. Gomez Anccas, E. A. MacPherson, J. Tegeler, K. Röbert, M. Fischer, C. A. Hans, D. Schulz

发表年份
2026
访问权限
开放获取

摘要

Synchronisation of parallel grid-forming inverters is crucial for stable operation of future power systems. This includes accurate and robust reactive power sharing under realistic operating conditions such as impedance mismatch and communication constraints. In this work, reactive power sharing by virtue of a distributed control law is investigated under line impedance mismatch. Furthermore, robustness and transient behaviour of the proposed approach are experimentally evaluated under communication-induced stressors including a fixed 3% packet loss and communication delays ranging from 50 ms to 100 ms, artificially introduced through a software-defined overlay. The study is conducted in a low-voltage laboratory-scale microgrid comprising two parallel grid-forming inverters, an AC load, and a grid-following battery system acting as a reactive power injector. The results show reactive power sharing convergence up to 90 ms communication delay, with a stability boundary between 90 ms and 100 ms, which decreases with increasing integral gain.

关键词

eess.SY